Coordinated Operation of Parallel-Connected Inverters for Active Islanding Detection using High Frequency Signal Injection

dc.contributor.authorBriz del Blanco, Fernando 
dc.contributor.authorDíaz Reigosa, David 
dc.contributor.authorBlanco Charro, Cristian 
dc.contributor.authorGuerrero Muñoz, Juan Manuel 
dc.date.accessioned2015-04-17T07:47:15Z
dc.date.available2015-04-17T07:47:15Z
dc.date.issued2014
dc.identifier.citationIEEE Transactions on Industry Applications, 50(5), p. 3476-3484 (2014); doi:10.1109/TIA.2014.2305802
dc.identifier.issn0093-9994
dc.identifier.urihttp://hdl.handle.net/10651/30648
dc.description.abstractThe high-frequency impedance measured at the terminals of inverters connected in a microgrid by means of the injection of a small magnitude high-frequency voltage has been shown to be a reliable metric to detect islanding. While the implementation of this method is simple when only an inverter injects the high-frequency signal, this case is of limited applicability. On the other hand, several concerns arise when multiple inverters work in parallel, primarily due to risk interference among inverters. Islanding detection using high-frequency signal injection in microgrids with multiple parallel-connected inverters is studied in this paper. A strategy for the coordinated operation of the inverters without the need of communications or preestablished roles is proposed. Simulation and experimental results will be provided to demonstrate the viability of the concept
dc.description.sponsorshipThis work was supported in part by the Research, Technological Development and Innovation Programs of the Ministry of Science and Innovation under grant MICINN-10-CSD2009-00046 and of the Spanish Ministry of Science and Innovation-ERDF under grant MICINN-10-ENE2010-14941
dc.format.extentp. 3476-3484spa
dc.language.isoengspa
dc.publisherIEEE
dc.relation.ispartofIEEE Transactions on Industry Applications, 50(5)spa
dc.rights© IEEE
dc.titleCoordinated Operation of Parallel-Connected Inverters for Active Islanding Detection using High Frequency Signal Injectionspa
dc.typejournal article
dc.identifier.doi10.1109/TIA.2014.2305802
dc.relation.projectIDMEC/MICINN-10-CSD2009-00046
dc.relation.projectIDMEC/MICINN-10-ENE2010-14941
dc.relation.publisherversionhttp://dx.doi.org/10.1109/TIA.2014.2305802
dc.rights.accessRightsopen access